ENGINEERING HUB
Measure clearly.
Calculate consistently.
Practical SI tools for commissioning checks. Each result shows its assumptions and method so it can be checked against the approved design.
CALCULATOR
Pump differential total head
Calculate the energy rise between suction and discharge measurements, including velocity and elevation corrections.
Method and scope
H = (p_d − p_s)/(ρg) + (v_d² − v_s²)/(2g) + (z_d − z_s) + h_remote. g = 9.80665 m/s².
Use gauge pressures with a common reference and a known steady liquid flow. Pressure-tap elevations must match the pressure readings. This is not an NPSH or pump selection calculation.
The pre-filled numbers are illustrative examples. Replace them with measured values or verified project inputs. Calculations do not save data or alter equipment.